Fireye Burner Logix Programmer – YP100
Need help selecting your product?
                            $1,675
            
                             Vendor: Fireye
                        
            
                            Description
The Fireye BurnerLogix YP100 programmer is a plug-in module for the YB110/YB230 (and ZB110/ZB230) chassis. It manages burner sequencing, purge and ignition timing, and flame-safety logic for industrial burner systems. Interchangeable YP modules let you tailor functions and flame-failure response times to the application.
Available Models & Functions
- YP100 – Non-recycle operation, modulation, open damper proving, 4-second FFRT.
 - YP102 – Non-recycle, modulation, open damper proving, 2-second FFRT.
 - YP112 – Non-recycle, modulation, open damper proving, 2-second FFRT.
 - YP113 – Non-recycle, modulation, open damper proving, 1-second FFRT.
 - YP115 – Non-recycle, modulation, open damper proving, 1-second FFRT.
 - YP118 – Non-recycle, modulation, open damper proving, indefinite pilot hold, revert-to-pilot, 1-second FFRT.
 - YP120 – Non-recycle, modulation, open damper proving, 1-second FFRT.
 - YP138 – Non-recycle, modulation, open damper proving, indefinite pilot hold, revert-to-pilot, 4-second FFRT.
 - YP148 – Non-recycle, modulation, open damper proving, fuel-selection switch, valve-prove test, low-gas-pressure check (active high), Burner On/Off via keypad, 4-second FFRT.
 - YP183 – As YP138, but removing voltage on terminal 16 suspends pilot-hold during light-off; terminal W used for purge-complete.
 - YP184 – As YP148, but low-gas-pressure check is active low; 4-second FFRT.
 - YP200 – Recycle operation, modulation, 4-second FFRT.
 - YP202 – Recycle operation, modulation, 2-second FFRT.
 - YP300 – Recycle operation, low-fire start, early spark termination, 4-second FFRT.
 - YP302 – Recycle operation, low-fire start, early spark termination, 2-second FFRT.
 
Applications & Benefits
- Safe sequencing of purge, ignition, pilot/main flame, and run cycles.
 - Selectable timings (PTFI/MTFI), purge/post-purge, and interlock logic via keypad/display.
 - Modular swap-out to change functions without replacing the chassis.