Honeywell RM7800 Controllers

Need help selecting your product?

Send an Email Call (804) 550-7143

Honeywell RM7800 Series Burner Management Controllers

The 7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications. The 7800-series are enabled for remote monitoring via the Thermal IQ Honeywell Connected Plant solution. For all type of burners with unlimited capacity.

Segment Use – RM7800 Family

The RM7800 family is used as the core burner programmer/primary platform with variants for Energy Saving Purge (ESP), Low-Fire hold (LF), and enhanced versions. Integrates with Q7800 bases, S7800 display modules, ST7800 purge timers, and R78xx flame amplifiers.

Features & Benefits

  • Modular design with plug-in modules
  • Selectable pre-purge time via ST7800A1xxx/U
  • Accepts Honeywell optical flame detectors and flame rods
  • Lockout history, flame signal, and hours viewable on S7800 display or via communications

Approvals

  • CE approved according EN 298 (EU models with correct amplifier & sensor)
  • SIL-3 Capable (except EC/RM7823 flame switches)
  • APAVE accepted (EU models only)
  • CSA/UL approved (US models only)

Protection Class & Environment

  • Europe: IP00; Americas: NEMA 1
  • Ambient temperature: -40 to 60 °C; Max humidity: 85 %RH

Failure Response Times (FFRT)

  • EU: 1.0 or 2.0 s (amplifier dependent)
  • US: 0.8 or 3.0 s (amplifier dependent)

RM7800 Models & Functions

  • RM7800E1010/U — BURNER MOD FULL; ESP; S7800; 120V; UL
  • RM7800E2010/U — BURNER MOD FULL; ESP; S7800; 120V; UL
  • RM7800G1018/U — BURNER MOD FULL; LF; S7800; 120V; UL
  • RM7800G2018/U — BURNER MOD FULL; LF; S7800; 120V; UL
  • RM7800L1012/U — BURNER MOD FULL; S7800; 120V; UL
  • RM7800L1053/U — BURNER MOD FULL; S7800; 120V; UL
  • RM7800L1087/U — ENH BURNER MOD. FULL; S7800; 120V; UL
  • RM7800L2012/U — BURNER MOD FULL; S7800; 120V; UL
  • RM7800L2053/U — BURNER MOD FULL; S7800; 120V; UL
  • RM7800L2087/U — ENH. BURNER MOD. FULL; S7800; 120V; UL
  • RM7800M1011/U — BURNER MOD ON/OFF; S7800; 120V; UL
  • RM7800M2011/U — BURNER MOD ON/OFF; S7800; 120V; UL

Documentation