HTS IFM – S70X/S80X Series Viewing Heads
Need help selecting your product?
Overview
The Honeywell S70X/S80X Series are single-channel viewing heads designed for industrial flame monitoring on gas or oil fired burners. Available in UV or IR sensing configurations, these viewing heads are used in conjunction with 700, 800, P531, or P532 signal processors and are well suited for single-fuel applications where a high level of flame discrimination is not required.
UV models utilize a UVTron sensor with pulse technology, making them especially effective for low-NOx burners with small or slow-moving flames. IR models use a germanium photodiode with flicker sensitivity for reliable detection across a broad spectral range. The S70X series features an aluminum body with over-center latch mounting, while the S80X series uses a stainless steel body with twist-lock mounting for higher-pressure applications.
Features & Benefits
- Available in IR (S702, S802) and UV (S706, S806) sensor configurations — provides application flexibility for gas or oil fired burners
- Electronic self-check on all models (no mechanical shutter) — simplifies maintenance and improves system reliability
- UV models use UVTron pulse technology — effective for low-NOx burners with small or slow-moving flames
- IR models use germanium photodiode with high-pass filter at 33 Hz — reliable flicker-based detection across a 950–1710 nm spectral range
- SIL 3 capable (S702/S802 and S706/S806 families) — supports safety system requirements
- S70X models: 1.48 in barrel diameter, aluminum housing — lightweight and economical
- S80X models: 1.14 in barrel diameter, stainless steel housing — rated to 90 psi, suited for higher-pressure environments
- PF models include factory-installed 10 ft cable — reduces field wiring time during installation
- Quick-disconnect cable with dual LED indicators (green: flame pulses; orange: self-check pulse) — assists setup and verification
- IP64 environmental rating when properly connected — suitable for industrial environments
- CSA, IECEx, and NCC/Inmetro hazardous location approvals — supports use in classified areas
Technical Specifications
- Ambient Temperature Range: -40 to +185°F (-40 to +85°C)
- Environmental Rating: IP64 (connector ring properly tightened, shielded cable installed)
- IR Sensor Type: Germanium photodiode; spectral response 950–1710 nm, peak at 1400 nm; high-pass filter at 33 Hz
- UV Sensor Type: UVTron; spectral response 185–260 nm, peak at 210 nm
- IR Field of View: 1° angle of view (1.45 in at 6 ft)
- UV Field of View: 5° angle of view (1 in per foot)
- S70X Pressure Rating: Lens withstands 50 psi
- S80X Pressure Rating: Lens withstands 90 psi (with correct compression ring)
- Power Supply: 24 VDC supplied by signal processor (700/800 SP)
- Purge Air Requirement: 5 SCFM at approximately 1 in. above burner pressure; air must be clean and dry
- Mounting Connection: 1/2 in NPT-F (sighting pipe); 1/4 in NPT-F (purge air)
- Cable: C330S — 4-conductor shielded with drain; ITC/CIC rated for hazardous locations
- UV Tube Service Life: 10,000–50,000 hours depending on operating conditions; monthly sensitivity check recommended
- Proof Test Interval: 1 to 5 years depending on safety system requirements
- Hazardous Location Approvals: CSA Class I, Div 2, Groups A, B, C, D, T4A; IECEx Ex nA IIC T4/T5 Gc; NCC/Inmetro Ex ec IIC T4 Gc
- Safety Rating: SIL 3 Capable (S702/S802 and S706/S806 families)
- Compatible Signal Processors: Model 700ACSP, 700DCSP, 800, P531, P532
Applications
- Industrial gas and oil fired burners requiring single-channel flame monitoring
- Low-NOx burner applications with small or slow-moving flames (UV models)
- Single-fuel combustion systems where high flame discrimination is not required
- Burner management systems requiring SIL 3 capable flame detection
- Hazardous location installations requiring CSA or IECEx certified equipment
- High-pressure burner front applications (S80X stainless steel series)
Models / Configurations
- S702 – 700 Series IR viewing head; aluminum body, 1.48 in barrel diameter; field-wired connector
- S702PF – 700 Series IR viewing head with factory-installed 10 ft cable; aluminum body
- S706 – 700 Series UV viewing head; aluminum body, 1.48 in barrel diameter; field-wired connector
- S706PF – 700 Series UV viewing head with factory-installed 10 ft cable; aluminum body
- S706PF-050 – 700 Series UV viewing head with factory-installed 50 ft cable; aluminum body
- S802 – 800 Series IR viewing head; stainless steel body, 1.14 in barrel diameter; rated to 90 psi
- S806 – 800 Series UV viewing head; stainless steel body, 1.14 in barrel diameter; rated to 90 psi
S70X/S80X Series Accessories
- ASY782 – Quick-disconnect cable with LED indicators and 15 ft cable for S700/S800 series viewing heads
- ASY784 – S700/S800 connector kit without cable
- ASY785-100 – Connector cable, 100 ft
- R-518-CL13-HTG – 1/2 in NPT lock coupling with high temperature gasket