HTS Maxon Direct Fired Furnace Burners – Multifire (Discontinued)

Need help selecting your product?

Send an Email Call (804) 550-7143

Discontinued Product Notice: The Honeywell Maxon Multifire dual-fuel high-temperature burner series has been discontinued. Information below is provided for legacy reference and replacement planning.

Features & Benefits

  • Dual-fuel capability: natural gas or light oil (#2); heavy oil option on select model (6″-HO).
  • Nozzle-mix refractory block design for stable flame in high-temperature furnaces.
  • Five body sizes with “on-ratio” capacities up to 17,500,000 BTU/h (≈5,120 kW) per burner.
  • Oil atomization using low-pressure combustion air—no steam or compressed air required.
  • Externally mounted gas pilot (sealed-port or boosted) with UV supervision; oil-only ignition is not permitted.

Model Overview

  • Sizes: 2″, 3″, 4″, 6″, 8″ bodies.
  • Versions:
    • Multifire (standard dual-fuel)
    • Multifire II 6″-HC (high-capacity, dual-fuel)
    • Multifire III (dual-fuel)
    • Multifire 6″-HO (heavy-oil only; cannot operate on gas)
  • Connections: ANSI or ISO; sizes over 2″ offered threaded or flanged.
  • Block options: Square (≤4″) or cylindrical (>4″) refractory blocks; optional carbon-steel or stainless block sleeves for thin/soft walls.

Technical Specifications

  • Fuels: Natural gas; light oil (#2). Heavy oils (#4 and higher) only on 6″-HO, heated to ≤50 SSU viscosity at the burner inlet.
  • Typical max “on-ratio” capacity: up to 17.5 MMBtu/h per burner (application dependent).
  • Combustion air differential pressure (at max): approximately 24–38 in. w.c., depending on size/version.
  • Ignition: Natural gas pilot (sealed-port or boosted). Oil-only ignition not allowed.
  • Materials (wetted/major components): Housing—gray iron; gas nozzle—carbon steel; air orifice—carbon steel; block sleeve—carbon or stainless steel; burner block—castable refractory.

Applications

  • High-temperature furnaces requiring uniformity: forge, annealing, melting, ceramic kilns, lehrs.
  • Fume/waste incinerators.
  • Air-heating systems (fresh-air streams) with appropriate flame protection sleeves.

Documentation

  • Data Sheet – Multifire (Discontinued) documents library (EN).
  • Technical Information – High Temperature Burners – MULTIFIRE® (specs, sizing, pilots, materials).

Additional Information

  • Status: Discontinued / archived in Honeywell Thermal Solutions Docuthek.
  • For retrofit or replacement selection, reference fuel, capacity, and air pressure requirements from the Technical Information sheet and match to current HTS burner families. Contact Martin Control for support.

Questions?

Call us at (804) 406-4103 or send us a message here!